4011, 4011D, 4012, 4013, 4015, 4015T, 4016,
4017, 4017+, 4018, 4018+, 4018M, 4019+
$AAM
Name
Read Module Name command
Description
The command requests the analog input module at address
AA to return its name.
Syntax
$AAM (cr)
$
AA
address of the analog input module that you want to
interrogate.
M
(cr)
Response
!AA(Module Name)(cr)
There is no response if the module detects a syntax error or
communication error, or if the specified address does not
exist.
!
received.
AA
address of an analog input module.
(Module Name)
(cr)
5-12
ADAM 4000 Series User's Manual
is a delimiter character.
(range 00-FF) represents the 2-character hexadecimal
is the Read Module Name command.
is the terminating character, carriage return (ODh).
is a delimiter character indicating a valid command was
(range 00-FF) represents the 2-character hexadecimal
is the name of the module at address AA.
is the terminating character, carriage return (ODh).
if the command is valid.