ADAM-4080D Command Table (Continued)
Command Syntax
@AAEAT
@AADA
@AACA
@AAPA(data)
@AASA(data)
@AARP
@AARA
@AADO(data)
@AADI
Command Name
Enable Alarm
Disable Alarm
Clear Latch Alarm
Set Low-Alarm
Count Value of
Counter 0
Set High-Alarm
Count Value of
Counter 0
Read Low-Alarm
Count Value of
Counter 0
Read High-Alarm
Count Value of
Counter 0
Set Digital Output
Values
Read Digital Output
and Alarm Status
Command Description
Enable the alarm in either
momentary or latching mode
Disable all alarm functions
The latch alarm is reset
Downloads the low-alarm count
value for counter 0 of the specified
counter/frequency module
Downloads the high-alarm count
value for counter 0 of the specified
counter/frequency module
Ask the addressed module to
return its low-alarm count value for
counter 0
Ask the addressed module to
return its high-alarm count value
for counter 0
Set the values of the module's two
digital outputs(ON or OFF)
Ask the module to return the status
state of its two digital outputs and
the status of its alarm.
Chapter 4 Command Set 4-43