Advantech Data Acquisition Modules ADAM 4000 User Manual page 159

Advantech data acquisition modules user's manual
Table of Contents

Advertisement

4011, 4011D, 4012, 4013, 4015, 4015T, 4016,
4017, 4017+, 4018, 4018+, 4019+
#AA
Name
Analog Data In command
Description
The command will return the input value from a specified
(AA) module in the currently configured data format.
Syntax
#AA(cr)
#
AA
address of an analog input module.
(cr)
Response
>(data)(cr)
There is no response if the module detects a syntax error or
communication error or if the specified address does not
exist.
>
(data)
the interrogated module.
(For data formats, see Appendix B).
(cr)
Example
command: #21(cr)
response:
The command interrogates the analog input module at
address 21h for its input values of all channels.
The analog input module responds with channels from 0 to
7 with +7.2111 volts, +7.2567 volts, +7.3125 volts,
+7.1000 volts, +7.4712 volts, +7.2555 volts, +7.1234 volts
and +7.5678 volts.
is a delimiter character.
(range 00-FF) represents the 2-character hexadecimal
is the terminating character, carriage return (0Dh).
is a delimiter character.
is the input value in the configured data format of
is the terminating character, carriage return (0Dh).
>+7.2111+7.2567+7.3125+7.1000
+7.4712+7.2555+7.1234+7.5678 (cr)