Advantech Data Acquisition Modules ADAM 4000 User Manual page 151

Advantech data acquisition modules user's manual
Table of Contents

Advertisement

4011, 4011D, 4012, 4013, 4015, 4015T, 4016,
4017, 4017+, 4018, 4018+, 4018M, 4019+
%AANNTTCCFF
Response
!AA(cr)
?AA(cr)
terminal was not grounded when attempting to change baud
rate or checksum settings.
There is no response if the module detects a syntax error or
communication error or if the specified address does not
exist.
!
received.
? delimiter character indicates the command was invalid
AA
address of an analog input module.
(cr)
Example
command:
response:
The ADAM-4011 module with address 23h is configured to
a new address of 24h, an input range ±2.5 V, baud rate
9600, integration time 50 ms (60 Hz), engineering units
data format and no checksum checking or generation.
The response indicates that the command was received.
Wait 7 seconds to let the new configuration settings take
effect before issuing a new command to the module.
NOTICE: Only ADAM-4011, ADAM-4011D, ADAM-4012, ADAM-4013,
ADAM-4016 and ADAM-4018+ support "% of FSR" and "two's
complement of hexadecimal" Data Format.
NOTICE: An analog input module requires a maximum of 7 seconds to
perform auto calibration and ranging after it is reconfigured.
During this time span, the module cannot be addressed to
perform any other actions.
NOTICE: All configuration parameters can be changed dynamically,
except checksum and baud rate parameters. They can only be
altered when the INIT* terminal is grounded. (Refer to Baud
rate and Checksum configuration in Chapter 2, for the correct
procedure)
if the command is valid.
if an invalid parameter was entered or if the INIT*
delimiter character indicates a valid command was
(range 00-FF) represents the 2-character hexadecimal
is the terminating character, carriage return (0Dh)
%2324050600(cr)
!24(cr)
5-5
ADAM 4000 Series User's Manual