Calibration
Module
4013
8-6 ADAM 4000 Series User's Manual
Table 8-2 Calibration Resistance
Input
Input Range
Range
Code
(Hex)
Pt, -100~100 ℃
20
a = 0.00385
Pt, 0~100 ℃
21
a = 0.00385
Pt, 0~200 ℃
22
a = 0.00385
Pt, 0~600 ℃
23
a = 0.00385
Pt, -100~100 ℃
24
a = 0.003916
Pt, 0~100 ℃
25
a = 0.003916
Pt, 0~200 ℃
26
a = 0.003916
Pt, 0~200 ℃
27
a = 0.003916
Ni, -80~100 ℃
28
Ni, 0~100 ℃
29
Span
Offset
Calibration
Calibration
Resistance
Resistance
140 Ω
60 Ω
140 Ω
60 Ω
200 Ω
60 Ω
440 Ω
60 Ω
140 Ω
60 Ω
140 Ω
60 Ω
200 Ω
60 Ω
440 Ω
60 Ω
200 Ω
60 Ω
200 Ω
60 Ω