4018M
@AASO
Name
Set Memory Operation Mode command
Description
Sets the operation mode of the analog input data logger at
address AA to Start or Stop.
Syntax
@AASO(cr)
@
AA
address of an analog input data logger.
S
O
'1': enables the recording of data.
'0': disables the recording of data.
(cr)
Response
!AA(cr)
?AA(cr)
response if the module detects a syntax error or
communication error or if the specified address does not
exist.
!
received.
?
invalid.
AA
address of an analog input data logger.
(cr)
Example
command:
response:
The command enables the analog input data logger at
address 03 to record data.
The response indicates that the command was received.
5-38
ADAM 4000 Series User's Manual
is a delimiter character.
(range 00-FF) represents the 2-character hexadecimal
is the Set Memory Operation Mode command.
represents the operation mode:
is the terminating character, carriage return (0Dh).
if the command is valid.
if an invalid parameter was entered. There is no
is a delimiter character indicating a valid command was
is a delimiter character indicating the command was
(range 00-FF) represents the 2-character hexadecimal
is the terminating character, carriage return (0Dh).
@03S1(cr)
!03(cr)