Advantech Data Acquisition Modules ADAM 4000 User Manual page 111

Advantech data acquisition modules user's manual
Table of Contents

Advertisement

Command Set
ADAM-4012 Command Table
Command Syntax
%AANNTTCCFF
#AA
$AA0
$AA1
#**
$AA4
$AA2
$AAF
$AAM
(Continued on following page)
4-8 ADAM 4000 Series User's Manual
Command Name
Configuration
Analog Data In
Span Calibration
Offset Calibration
Synchronized
Sampling
Read Synchronized
Data
Configuration Status
Read Firmware
Version
Read Module Name
Command Description
Sets the address, input range,baud
rate, data format, checksum
status, and/or integration time for a
specified analog input module
Returns the input value from a
specified analog input module in
the currently configured data
format
Calibrates an analog input module
to correct for gain errors
Calibrates an analog input module
to correct for offset errors
Orders all analog input modules to
sample their input values and store
them in special registers
Returns the value that was stored
in the specified module's register
after the #** command
Returns the configuration
parameters for the specified
analog input module
Return the firmware version code
from the specified analog input
module
Return the module name from the
specified analog input module
Page No.
5-4
5-14
5-19
5-20
5-21
5-22
5-10
5-12
5-13

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Data Acquisition Modules ADAM 4000 and is the answer not in the manual?

Table of Contents

Save PDF