Adam-4060 Relay Output Module - Advantech Data Acquisition Modules ADAM 4000 User Manual

Advantech data acquisition modules user's manual
Table of Contents

Advertisement

A.17 ADAM-4060 Relay Output Module
Table A-21 ADAM-4060 Specifications
DO channel number
Input
speed (bps)
Maximum distance
Contact rating
(Resistive)
Breakdown voltage
Relay on time (typical)
Relay off time (typical)
Total switching time
Insulation resistance
Support protocol
Watchdog timer
Power supply
Power consumption
4 channel relay
(2 form A, 2 form C)
RS-485 (2-wire)
1200, 2400, 4800, 9600, 19.2K,
38.4K, 57.6K, 115.2K
4000 ft. (1200 m)
AC: 0.6 A@125 V
0.3 A@250 V
DC: 2 A@30 V
0.6 A@ 110 V
500 V
(50/60 Hz)
AC
3 ms
2 ms
10 ms
1 GΩ minimum at 500 V
ADAM ASCII
1.6 second (System)
+10 to +30 V
DC
0.8 W @ 24 V
DC
Appendix A Technical Specification A-41
Appendix A
DC
(non-regulated)