4015, 4015T
$AAS1
Name
Reload Default Calibrating Parameter command
Description
Reload factory default calibrating parameter to overwrite
current calibrating parameter.
Syntax
$AAS1(cr)
$
AA
address of the analog input module which is to be reloaded.
S1
(cr)
Response
!AA(cr)
?AA(cr)
There is no response if the module detects a syntax error or
communication error or if the specified address does not
exist.
!
received.
?
AA
address of the analog input module.
(cr)
is a delimiter character.
(range 00-FF) represents the 2-character hexadecimal
is the Reload Calibrating Parameter command.
is the terminating character, carriage return (0Dh).
if the command was valid.
if an invalid operation was entered.
delimiter character indicates a valid command was
delimiter character indicates the command was invalid.
(range 00-FF) represents the 2-character hexadecimal
represents terminating character, carriage return (0Dh).
5-33
ADAM 4000 Series User's Manual
5
Chapter