Advantech Data Acquisition Modules ADAM 4000 User Manual page 192

Advantech data acquisition modules user's manual
Table of Contents

Advertisement

4018M
@AABC
Name
Read Alarm Limit command
Description
Request the alarm limits for the specified channel in the
analog input data logger at address AA.
Syntax
@AABC(cr)
@
AA
address of an analog input data logger.
B
C
(cr)
Response
!AASDHHHHTEIIII
!
received.
AA
address of an analog input data logger.
S
'+' is for positive, and '-' is for negative.
D
value is from 0 to 5.
HHHH
high alarm limit.
T
'+' is for positive, and '-' is for negative.
E
value is from 0 to 5.
IIII
alarm limit.
(cr)
5-46
ADAM 4000 Series User's Manual
is a delimiter character.
(range 00-FF) represents the 2-character hexadecimal
is the Read Alarm Limit command.
represents the channel index. Its value is from 0 to 7.
is the terminating character, carriage return (0Dh).
is a delimiter character indicating a valid command was
(range 00-FF) represents the 2-character hexadecimal
represents the sign of the high alarm limit.
represents the decimal point of the high alarm limit. Its
represents the 4-character hexadecimal number of
represents the sign of the low alarm limit.
represents the decimal point of the low alarm limit. Its
represents the 4-character hexadecimal number of low
is the terminating character, carriage return (0Dh).

Advertisement

Table of Contents
loading

Table of Contents