5.1 Analog Input Common Command Set
Command
Description
Syntax
%AANNTTCCF
Sets the address, input range,
F
baud rate, data format,
checksum status, and/or
integration time for a specified
analog input module
$AA2
Returns the configuration
parameters for the specified
analog input module
$AAF
Returns the firmware version
code from the specified analog
input module
$AAM
Returns the module name from
the specified analog input
module
#AA
Returns the input value from a
specified analog input moudule
in the currently configured data
format
#AAN
Returns the input value from
channel number n of the
specified analog input module
#AA5VV
Enables/disables multiplexing
simultaneously for separate
channels of the specified input
module
$AA6
Ask the specified input module
to return the status of all eight
channels
$AA0
Calibrate the analog input
module to correct for gain errors
$AA1
Calibrate the analog input
module to correct for offset
errors.
#**
Orders all analog input modules
to sample their input values and
store them in special registers
(Continued on following page)
5-2
ADAM 4000 Series User's Manual
I/O Module
4011, 4011D, 4012, 4013, 4015,
4015T, 4016, 4017, 4017+, 4018,
4018+, 4018M, 4019+
4011, 4011D, 4012, 4013, 4015,
4015T, 4016, 4017, 4017+, 4018,
4018+, 4018M, 4019+
4011, 4011D, 4012, 4013, 4015,
4015T, 4016, 4017, 4017+, 4018,
4018+, 4018M, 4019+
4011, 4011D, 4012, 4013, 4015,
4015T, 4016, 4017, 4017+, 4018,
4018+, 4018M, 4019+
4011, 4011D, 4012, 4013, 4015,
4015T, 4016, 4017, 4017+, 4018,
4018+, 4019+
4015, 4015T, 4017, 4017+, 4018,
4018+, 4018M, 4019+
4015, 4015T, 4017, 4017+, 4018,
4018+, 4018M, 4019+
4015, 4015T, 4017, 4017+, 4018+,
4018, 4018M, 4019+
4011, 4011D, 4012, 4013, 4016,
4017, 4018, 4018M
4011, 4011D, 4012, 4013, 4016,
4017, 4018, 4018M
4011, 4011D, 4012, 4013, 4015,
4015T, 4016
Need help?
Do you have a question about the Data Acquisition Modules ADAM 4000 and is the answer not in the manual?