Advantech Data Acquisition Modules ADAM 4000 User Manual page 234

Advantech data acquisition modules user's manual
Table of Contents

Advertisement

4024
ADAM-4024 Command Review: (Continued)
Command Set
Function
#AAECn(data)
Set data As CHn Emergency Stop Data
#**
Synchronous Sample IDI
$AA0Cn
Set Current Trim Data As CHn 4m A
Calibration Parameter/EEPROM
$AA1Cn
Set Current Trim Data As CHn 20m A
Calibration Parameter/EPROM
$AA2
Read Back Module Status
$AA3Cn(m)
Set Trim Data For CHn
m :0 ~ 127
And If Negative Then Add 0x80 (m =xx )
Ex.m=89 → -9 m=09 → +9
$AA4
Read Back The IDI Input By Synchronous
Command (#**)
$AA5
Checks the Reset Status of the analog
output module to see whether it has been
reset since the last Reset Status
command was issued.
$AA6Cn
Read Back CHn Last Output Value
$AA7CnRxx
Set CHn Output Type
AA:
Cn:
C: Prefix Command String
n = 0,1,2,3
Rxx:
R: Prefix Command String
xx = 32
xx = 30
xx = 31
6-20 ADAM 4000 Series User's Manual
Current Module Address
Channel
Output Type (Range)
-10 V ~ +10 V
0 ~ 20 mA
4 ~ 20 mA
Analog Output Module Command Set
Response
!AAECn (data)
No Response
!AA
!AA
!AATTCCFF
!AA
!AAx
!AAS
!AA(data)
!AA
Exam ple
#02EC2 +07.456
#02EC1 -03.454
#02EC0 +11.234
#**
$020C2
$021C2
$022
$02308
$024
$025
$026C2
$027C2R32