Advantech Data Acquisition Modules ADAM 4000 User Manual page 309

Advantech data acquisition modules user's manual
Table of Contents

Advertisement

4080D
@AAPA(data)
Name
Set Low-alarm Count Value for Counter 0 command
Description
Set the low-alarm count value for counter 0 of the specified
counter module.
Syntax
@AAPA(data)(cr)
@
AA
address of the module.
PA
command.
(data)
eight hexadecimal digits. This value should be lower than
the high alarm value.
(cr)
Response
!AA(cr)
There is no response if the module detects a syntax or
communication error, or even if the specified address does
not exist.
!
AA
address of the module.
(cr)
Example
command: @12PA0000FFFF(cr)
response:
The
0000FFFF(hex) for channel 0 of the counter modules at
address 12. The addressed module replies that the
command has been received.
7-74 ADAM 4000 Series User's Manual
is a delimiter character.
(range 00-FF) represents the 2-character hexadecimal
is the Set Low-alarm Count Value for Counter 0
is the low-alarm count value which must consist of
is the terminating character, carriage return (0Dh).
if the command is valid.
is a delimiter character which indicates a valid command
(range 00-FF) represents the 2-character hexadecimal
is the terminating character, carriage return (0Dh).
!12(cr)
command
Digital I/O and Relay Output
Counter/Frequency Command Set
sets
the
low-alarm
count
number

Advertisement

Table of Contents
loading