4016
$AA6
Name
Get Excitation Voltage Output Value command
Description
The addressed strain gauge input module is instructed to
return the latest output value it received from Excitation
Voltage Output command. If the module hasn't received an
Excitation Voltage Output command since startup, it will
return its Start-up Output value.
Syntax
$AA6(cr)
$
AA
address of the strain gauge input module.
6
(cr)
Response
!AA(data)(cr)
?AA(cr)
There is no response if the module detects a syntax error or
communication error or if the specified address does not
exist.
!
received.
?
AA
address of the strain gauge input module.
(data)
The format of the data is in engineering unit.
(cr)
Example
command:
response:
The command tells the strain gauge input module at address
0Ah to return the last excitation voltage output value it
received from an Excitation Voltage Output command. The
strain gauge input module returns the value +03.000V.
5-62
ADAM 4000 Series User's Manual
is a delimiter character.
(range 00-FF) represents the 2-character hexadecimal
is the Get Excitation Voltage Output command.
is the terminating character, carriage return (0Dh)
if the command is valid.
if an invalid command was issued.
delimiter character indicates a valid command was
delimiter character indicates the command was invalid.
(range 00-FF) represents the 2-character hexadecimal
is the value that is returned by analog output channel.
is the terminating character, carriage return (0Dh)
$0A6(cr)
!0A+03.000(cr)