4011, 4011D, 4012, 4013, 4015, 4015T, 4016,
4017, 4017+, 4018, 4018+, 4018M, 4019+
%AANNTTCCFF
Name
Configuration command
Description
Sets address, input range, baud rate, data format, checksum
status, and/or integration time for an analog input module.
Syntax
%AANNTTCCFF(cr)
%
AA
address of the analog input module you want to configure.
NN
input module. Range is from 00h to FFh.
TT
4019 must be 00)
(Refer to Table 5-1 on Page 5-6)
CC
(Refer to Table 5-2 on Page 5-8)
FF
representing the data format, checksum status and
integration time. The layout of the 8-bit parameter is shown
in Figure 5-1. Bits 2 through 5 are not used and are set to 0.
(cr)
7
6
Checksum status
0: Disabled
1: Enabled
Integration time
0: 50 ms (Operation under 60 Hz power)
1: 60 ms (Operation under 50 Hz power)
Figure 5-1 Data format for FF (8-bit parameter)
5-4
ADAM 4000 Series User's Manual
is a delimiter character.
(range 00-FF) represents the 2-character hexadecimal
represents the new hexadecimal address of the analog
represents the type (input range) code. (Note: 4015 and
represents the baud rate code.
is a hexadecimal number that equals the 8-bit parameter
is the terminating character, carriage return (0Dh)
5
4
not used
3
2
1
Data Format
00: Engineering units
01: % of FSR
10: two's complement of hexadecimal
11: Ohms (for 4013 and 4015)
0