Advantech Data Acquisition Modules ADAM 4000 User Manual page 258

Advantech data acquisition modules user's manual
Table of Contents

Advertisement

4056SO
$AAE0
Name
Read and Clear over Current Status Flag command
Description
Read the Over Current Status Flag and Clear the Flag
simultaneously.
Syntax
$AAE0(cr)
$
is a delimiter character.
AA
address that you will access to.
E0
(cr)
Response
!AAX(cr):
?AA(cr):
X
X=0: No over current occur
X=1: DO0~3 has over current occurred
X=2: DO4~7 has over current occurred
X=4: DO8~11 has over current occurred
!
is a delimiter character which indicates a valid command
?
is a delimiter character which indicates an invalid command
(cr)
7-23 ADAM 4000 Series User's Manual
(range 00-FF) represents the 2-character hexadecimal
is the Read and Clear over Current Status Flag command.
is the terminating character, carriage return (ODh).
if the command is valid.
if an invalid command has been issued.
is one-hexadecimal character (range from 0 to 7)
is the terminating character, carriage return (ODh).
7
Chapter

Advertisement

Table of Contents
loading
Need help?