ADAM-4018+ Command Table (Continued)
Command Syntax
$AA1Ci
$AA7CiRrr
$AA8Ci
$AAXnnnn
$AAY
ADAM-4018+
Input range and external calibrating input source for each input type
Range
Input Range
bcode(Hex)
06
+/-20 mA
07
4~20 mA
14
Type J
Thermocouple
15
Type K
Thermocouple
16
Type T
Thermocouple
17
Type E
Thermocouple
18
Type R
Thermocouple
19
Type S
Thermocouple
20
Type B
Thermocouple
Command Name
Offset Calibration
Input Range Setting
Read Input Range
Set Communication
WDT
Get Communication
WDT Setting
Max. Signal
+20.000
+20.000
Command Description
Offset error calibrate of assignment
channel, User have to input the external
standard source for calibrating process
Input range setting individually
Get the input range of the assignment
channel
Set communication WDT cycle time from
0000 ~ 9999 (unit: 0.1 second. if value is
0000, the communication WDT function
will be disable)
Read the cycle time setting of
communication WDT
Min Signal
-20.000
+4.000