Module: ADAM-4016
1. Apply power to the strain gauge input module and let it warm up for
about 30 minutes.
2. Assure that the module is correctly installed.
voltmeter to the screw terminals of the module.
Voltmeter
-
Figure 8-7 Setup for Voltage Output Calibration
3. Execute the Zero Calibration command. This is done through the
ADAM utility software. (Please see "A/O 0V Calibration" option in
the Calibration sub-menu of the ADAM utility software.)
+
Figure 8-8 Zero Calibration
Chapter
Then, connect a
ADAM-4016
Chapter 8 Calibration 8-15