Advantech Data Acquisition Modules ADAM 4000 User Manual page 127

Advantech data acquisition modules user's manual
Table of Contents

Advertisement

Command Set
ADAM-4021 Command Table
Command Syntax
%AANNTTCCFF
#AA(data)
$AA4
$AA3(number of
counts)
$AA0
$AA1
$AA2
$AA6
$AA8
$AA5
$AAF
$AAM
4-24 ADAM 4000 Series User's Manual
Command Name
Configuration
Analog Data Out
Start-up output
current/voltage
configuration
Trim Calibration
4 mA Calibration
20 mA Calibration
Configuration
Status
Last Value
Readback
Current Readback
Reset Status
Read Firmware
Version
Read Module
Name
Command Description
Set the address, output range,
baud rate, data format, slew rate
and/or checksum status
Directs output data to a specified
module
Stores a default output value in a
specified module. The output
value will take effect upon startup.
Trims specified module a number
of units up/down
Tells the module to store
parameters for 4 mA Calibration
Tells the module to store
parameters for 20 mA Calibration
Reads configuration of specified
module
Returns either last value sent to
specified module by #AA
command, or start-up output
current/voltage
Returns measured value of the
current/voltage flowing through
current loop
Checks if module has been reset
since the last $AA5 command
Return the firmware version code
from the specified analog output
module
Return the module name from the
specified analog output module
Page
No.
6-3
6-6
6-8
6-9
6-11
6-12
6-13
6-14
6-15
6-16
6-17
6-18

Advertisement