Advantech Data Acquisition Modules ADAM 4000 User Manual page 230

Advantech data acquisition modules user's manual
Table of Contents

Advertisement

4021
$AA5
Name
Reset Status command
Description
Checks the Reset Status of the analog output module to see
whether it has been reset since the last Reset Status
command was issued.
Syntax
$AA5(cr)
$
AA
address of the analog output module who's Reset Status is
to be returned.
5
(cr)
Response
!AAS(cr)
?AA(cr)
There is no response if the module detects a syntax or
communication error, or even if the specified address does
not exist.
!
received.
?
AA
address of the analog output module.
S
output module. If S=1, the module is in reset mode since a
Reset Status command had been issued already. If S=0, the
module has not been reset since the last Reset Status
command was not issued.
(cr)
Example
command: $395(cr)
response:
The analog output module at address 39h was reset or
powered up after the last execution of the Reset Status
command. When the command is executed once more, the
analog output module will reply with !390(cr)
6-16 ADAM 4000 Series User's Manual
is a delimiter character.
(range 00-FF) represents the 2-character hexadecimal
is the Reset Status command.
is the terminating character, carriage return (0Dh).
if the command was valid.
if an invalid command was issued.
delimiter character indicates that a valid command was
delimiter character indicates that the command was valid.
(range 00-FF) represents the 2-character hexadecimal
represents the Status bit which is returned by the analog
is the terminating character, carriage return (0Dh).
!391(cr)
Analog Output Module Command Set