4015, 4015T, 4017+, 4018+, 4019+
$AA0Ci
Name
Single Channel Span Calibration command
Description
The command calibrates a specified channel to correct for
gain errors.
Syntax
$AA0Ci(cr)
$
AA
address of the analog input module which is to be
calibrated.
0
Ci
calibrate.
(cr)
Response
!AA(cr)
?AA(cr)
There is no response if the module detects a syntax error or
communication error or if the specified address does not
exist.
!
received.
?
AA
address of the analog input module.
(cr)
NOTICE: An analog input module requires a maximum of 7 seconds to
perform auto calibration and ranging after it received a Span
Calibration command. During this interval, the module can not
be addressed to perform any other actions.
5-26
ADAM 4000 Series User's Manual
is a delimiter character.
(range 00-FF) represents the 2-character hexadecimal
is the Single Channel Span Calibration command.
represents the specified input channel you want to
is the terminating character, carriage return (0Dh).
if the command was valid.
if an invalid operation was entered.
delimiter character indicates a valid command was
delimiter character indicates the command was invalid.
(range 00-FF) represents the 2-character hexadecimal
represents terminating character, carriage return (0Dh).
In order to successfully calibrate an analog input module's
input range, a proper calibration input signal should be
connected to the analog input module before and during the
calibration. (See also Chapter 8, Calibration)