Advantech Data Acquisition Modules ADAM 4000 User Manual page 307

Advantech data acquisition modules user's manual
Table of Contents

Advertisement

4080D
@AADA
Name
Disable Alarm command
Description
Disable all alarm functions for counter 0 of the addressed
counter module.
Syntax
@AADA(cr)
@
AA
address of the module.
DA
(cr)
Response
!AA(cr)
There is no response if the module detects a syntax or
communication error, or even if the specified address does
not exist.
!
AA
module.
(cr)
Example
command: @07DA(cr)
response:
The counter module at address 07h is instructed to disable
all alarm functions for channel 0. The module confirms by
disabling the alarm functions.
NOTICE: A counter module requires a maximum of two seconds after it
has received a Disable Alarm command before the settings take
effect. During this interval, the module cannot be addressed to
perform any other actions.
7-72 ADAM 4000 Series User's Manual
is a delimiter character.
(range 00-FF) represents the 2-character hexadecimal
is the Disable Alarm command.
represents terminating character, carriage return (0Dh).
if the command was valid.
is a delimiter character which indicates a valid command.
represents the 2-character hexadecimal address of the
represents terminating character, carriage return (0Dh).
!07(cr)
Digital I/O and Relay Output
Counter/Frequency Command Set