Advantech Data Acquisition Modules ADAM 4000 User Manual page 188

Advantech data acquisition modules user's manual
Table of Contents

Advertisement

4018M
@AARNNNN
Name
Read Record Content command
Description
Request the content of record NNNN stored in the analog
input data logger at address AA.
Syntax
@AARNNNN (cr)
@
AA
address of an analog input data logger.
R
NNNN
stored record index. Its value is from 0 to (total record
number - 1).
(cr)
NOTE:
NNNN is from 0 to 9470 for Standard Mode.
NNNN is from 0 to 4599 for Event Mode.
NNNN is from 0 to 7299 for Mixed Mode. (0-4999 are
data records, 5000-7299 are event records)
Response
!AACDHHHH(cr)
!AACDHHHHTTTTTTTT(cr)
event records.
!
received.
AA
address of an analog input module.
C
D
sign of the number HHHH. '0' means positive. '1' means
negative. Bits 1~3 represents the decimal point of the
number HHHH.
5-42
ADAM 4000 Series User's Manual
is a delimiter character.
(range 00-FF) represents the 2-character hexadecimal
identifies the Read Record Content command.
represents the 4-character hexadecimal number of
is the terminating character, carriage return (0Dh).
is a delimiter character indicating a valid command was
(range 00-FF) represents the 2-character hexadecimal
represents the channel index. Its value is from 0 to 7.
represents the 4-bit binary number. Bit 0 represents the
if the returned data are data records.
if the returned data are