4080, 4080D
$AA4S
Name
Enable/Disable Digital Filter command
Description
Enables or disables the digital filter of the counter/
frequency module.
Syntax
$AA4S(cr)
$
AA
address that you will access to.
4
S
S = 0 means disable filter
S = 1 means enable filter
(cr)
Response
!AA(cr)
There is no response if the module detects a syntax or
communication error, or even if the specified address does
not exist.
!
AA
address of the module.
(cr)
Example
command: $0340(cr)
response:
The command orders the counter/frequency module at
address 03 to disable its digital filter. The module returns
its address indicating that it has executed the command
successfully.
7-50 ADAM 4000 Series User's Manual
is a delimiter character.
(range 00-FF) represents the 2-character hexadecimal
is the Enable/Disable Filter command.
is the digital filter mode.
is the terminating character, carriage return (0Dh).
if the command is valid.
is a delimiter character which indicates a valid command.
(range 00-FF) represents the 2-character hexadecimal
is the terminating character, carriage return (0Dh).
!03(cr)
Digital I/O and Relay Output