4080, 4080D
$AAAG
Name
Set Gate Mode command
Description
Request the specified counter/frequency module to set its
gate to one of the three states, high, low or disabled.
Syntax
$AAAG(cr)
$
AA
address that you will access to.
A
G
G = 0 the gate is low
G = 1 the gate is high
G = 2 the gate is disabled
(cr) is the terminating character, carriage return (0Dh).
Response
!AA(cr)
There is no response if the module detects a syntax or
communication error, or even if the specified address does
not exist.
!
AA
address of the module.
(cr)
Example
command: $01A1(cr)
response:
The command requests the counter/frequency module at
address 01 to set its gate high. The module will reply with
an address indicating that it has executed the command.
7-41 ADAM 4000 Series User's Manual
is a delimiter character.
(range 00-FF) represents the 2-character hexadecimal
is the Gate Mode command.
determines the gate mode:
if the command is valid.
is a delimiter character which indicates a valid command.
(range 00-FF) represents the 2-character hexadecimal
is the terminating character, carriage return (0Dh).
!01(cr)
7
Chapter
Need help?
Do you have a question about the Data Acquisition Modules ADAM 4000 and is the answer not in the manual?