4015, 4015T, 4017+, 4018+, 4019+
$AA8Ci
Name
Read Single Channel Range Configuration command
Description
of the specified channel in an analog input module.
Syntax
$AA8Ci(cr)
$
AA
address of the analog input module which is to be read.
8
command.
Ci
(cr)
Response
!AACiRrr(cr)
?AA(cr)
There is no response if the module detects a syntax error or
communication error or if the specified address does not
exist.
!
received.
?
AA
address of the analog input module.
Ci
Rrr
channel.
(Refer to Table 5-1 on Page 5-6 to check range codes)
(cr)
Example
command: $028C5(cr)
response: !02C5R21(cr)
The command read the range of channel 5 in the analog
input module at address 02. The response "R21" means
Pt100 (IEC) 0 ~ 100 ℃.
This command read the input type and range configuration
is a delimiter character.
(range 00-FF) represents the 2-character hexadecimal
is the Read Single Channel Range Configuration
represents the specified input channel you want to read.
is the terminating character, carriage return (0Dh).
if the command was valid.
if an invalid operation was entered.
delimiter character indicates a valid command was
delimiter character indicates the command was invalid.
(range 00-FF) represents the 2-character hexadecimal
represents the specified input channel you read.
represents the type and range setting in the specified
represents terminating character, carriage return (0Dh).
5-29
ADAM 4000 Series User's Manual
5