4021
$AAM
Name
Read Module Name
Description
The command requests the analog output module at address
AA to return its name
Syntax
$AAM (cr)
$
AA
address that you want to access.
M
(cr)
Response
!AA(Module Name)(cr)
There is no response if the module detects a syntax or
communication error, or even if the specified address does
not exist.
!
was received.
AA
address of an analog output module.
(Module Name)
For example, 4021
(cr)
6-18 ADAM 4000 Series User's Manual
is a delimiter character.
(range 00-FF) represents the 2-character hexadecimal
is the Read Module Name command.
is the terminating character, carriage return (ODh)
is a delimiter character indicating that a valid command
(range 00-FF) represents the 2-character hexadecimal
is the name of the module at address AA.
is the terminating character, carriage return (ODh).