Technical Specifications
Table A-12 ADAM-4018M Range Accuracy for Thermocouple
Input
Range
Input Range
Code
(Hex)
J thermocouple
0E
0 to 760 ℃
K thermocouple
0F
0 to 1370 ℃
T thermocouple
10
-100 to 400 ℃
E thermocouple
11
0 to 1000 ℃
R thermocouple
12
500 to 1750 ℃
S thermocouple
13
500 to 1750 ℃
B thermocouple
14
500 to 1800 ℃
NOTE: Because the CJC sensor of ADAM-4018M is located in
the side of channel 0 to 4, the measurement will have the
difference ± 1 ℃ between channel 0 ~ 4 and channel 5 ~ 7.
A-20 ADAM 4000 Series User's Manual
Typical
Maximum
Accuracy
±1.0
±1.0
±1.0
±1.0
±1.2
±1.2
±2.0
Units
Error
±1.5
℃
±1.5
℃
±1.5
℃
±1.5
℃
±2.5
℃
±2.5
℃
±3.0
℃