Advantech Data Acquisition Modules ADAM 4000 User Manual page 198

Advantech data acquisition modules user's manual
Table of Contents

Advertisement

4011, 4011D, 4012, 4016
@AAEAT
Name
Enable Alarm command
Description
The addressed analog input module is instructed to enable
its alarm in either Latching or Momentary mode.
Syntax
@AAEAT(cr)
@
AA
address of an analog input module.
EA
T
Momentary alarm state, or L = Latching alarm state.
(cr)
Response
!AA(cr)
There is no response if the module detects a syntax error or
communication error or if the specified address does not
exist.
!
received.
AA
responding analog input module.
(cr)
Example
command:
response:
The analog input module at address 03h is instructed to
enable its alarm in Latching mode.
The module confirms that the command has been received.
NOTICE: An analog input module requires a maximum of 2 seconds after
it received an Enable Alarm command to let the settings take
effect . During this interval, the module can not be addressed to
perform any other actions.
5-52
ADAM 4000 Series User's Manual
is a delimiter character.
(range 00-FF) represents the 2-character hexadecimal
is the Enable Alarm command.
indicates alarm type and can have the value M =
represents terminating character, carriage return (0Dh).
if the command was valid.
delimiter character indicates a valid command was
represents the 2-character hexadecimal address of the
represents terminating character, carriage return (0Dh).
@03EAL(cr)
!03(cr)