4080
@AADAN
Name
Disable Alarm command
Description
Disable Alarm for the specified counter.
Syntax
@AADAN
@
AA
address of the module.
DAN
N = 0 Represents counter 0
N = 1 Represents counter 1
(cr)
Response
!AA(cr)
There is no response if the module detects a syntax or
communication error, or even if the specified address does
not exist.
!
AA
address of a counter module.
(cr)
Example
command: @12DA0(cr)
response:
7-65 ADAM 4000 Series User's Manual
(cr)
is a delimiter character.
(range 00-FF) represents the 2-character hexadecimal
is the Disable Alarm Mode command.
is the terminating character, carriage return (0Dh).
if the command is valid.
is a delimiter character which indicates a valid command.
(range 00-FF) represents the 2-character hexadecimal
is the terminating character, carriage return (0Dh).
!12(cr)
The counter module at address 12h is instructed to disable
the alarm functions for counter 0. The module confirms
that its alarm functions have been disabled.