Adam-4011D Thermocouple Input Module With Led; Display - Advantech Data Acquisition Modules ADAM 4000 User Manual

Advantech data acquisition modules user's manual
Table of Contents

Advertisement

A.2 ADAM-4011D
Table A-3 ADAM-4011D Specifications
T/C channel number
Input range
Output
speed (in bps)
Maximum distance
Accuracy
Zero drift
Span drift
Isolation-rated voltage
CMR @ 50/60 Hz
NMR @ 50/60 Hz
Resolution
Sampling rate
Input impedance
LED indicator
Digital output
Sink current
Power dissipation
Digital input
Logic level 0
Logic level 1
Pull up current
Event counter
Max. input frequency
Min. pulse width
Support protocol
Watchdog timer
Power supply
Power consumption
Burn-out detection
Thermocouple Input Module with LED

Display

1
J, K, T, E, R, S and B Thermocouple
±15 mV, ±50 mV, ±100 mV, ±500mV,
±1 V, ±2.5 V and ±20mA
RS-485 (2-Wire)
1200, 2400, 4800, 9600, 19.2K, 38.4K,
57.6K, 115.2K
4000 ft. (1200 m.)
±0.05% or better
±6 μV/
±25 ppm/
3000 V
DC
150 dB
100 dB
16-bit
10 samples/second
Voltage: 2 MΩ, Current: 125 Ω
5 digit readout
2 channels open collector to 30 V
30 mA maximum load
300 mW
1 channel
+1 V maximum
+3.5 to +30 V
0.5 mA
50 Hz
1 msec
ADAM ASCII
1.6 second (System)
+10 to +30 V
1.4 W @ 24 V
Yes
(non-regulated)
DC
DC
Appendix A Technical Specification A-5
Appendix A