OutputAmps(rms)
K0242
from evaluation of
actual-values
[500.8]
1
0
0
1) For
● no temperature sensor (P131 = 0)
and
● P383 ≥ 100 s
0) Otherwise
It is not possible to evaluate the motor temperature for
WARNING
encoder evaluations that are not inserted in slot C.
Encoder evaluation, slot C
X
Q.MotorTemp
5
P138
K
1
2
Protective functions
Part 2
Motor Cooling
Mot.Temp.T1
0 ... 1
0 ... 16 000 s
P382 (1)
P383 (100 s)
Motor Utilization
r008
i2t Calculation
Motor Temperat.
K0245
Motor Temperat.
r009
Select TmpSensor
0 ... 5
P131 (1)
Temperature
evaluation
X
3
KTY83 selected
3
4
Mot. Load Limits
0 ... 300 %
P384.1 (100 %)
A029:
Alarm motor overtemperature
1
0
F021:
Fault motor overtemperature
1
0
0 ... 300 %
P384.2 (100 %)
Mot. Load Limits
Mot Tmp Warning
0 ... 300 °C
P380 (100)
A023:
2 °C
Motor overtemperature
1
0
F020:
Motor overtemperature fault
1
0
0 ... 300 °C
P381 (120)
Mot Tmp Fault
max. temp = 140 °C
F020:
1
Motor overtemperature fault
0
min. temp = -55 °C
5
6
V2.5
fp_mc_491_e.vsd
18.01.06
n959.63 = P357
to status word 2, bit 25 [210.2]
to status word 2, bit 26 [210.2]
Motor temperature monitoring:
No temperature sensor:
P131 = 0
Monitoring with KTY84:
P131 = 1
PTC monitoring:
P131 = 2
Monitoring with PT100:
P131 = 3
Monitoring with KTY83:
P131 = 4
Coupling via Src Motor Temp.:
P131 = 5
to status word 2, bit 25 [210.2]
to status word 2, bit 26 [210.2]
7
Function diagram
MASTERDRIVES MC
8
- 491 -