Parameter
Description
P248*
BICO parameter for selecting the connector from which
S.DT1 Function
the input signal of the DT1 function is to be read in.
248
P249*
Function parameter for entering the smoothing time T1 of
DT1 Function T1
the DT1 function.
249
P250*
Function parameter for entering the differential time Td of
DT1 Function Td
the DT1 function.
250
P251*
Function parameter for entering the gain of the band-stop
Band-Stop Gain
filter.
251
P252*
BICO parameter for selecting the connector from which
S.Band-Stop
the input signal for the band-stop filter is to be read in. A
band-stop filter can be used specifically to prevent
252
excitation of mechanical or electrical resonances.
P253*
Quality of the band-stop filter
Qty Band-Stop
Function parameter for entering the quality of the band-
stop filter. The quality of the band-stop filter indicates how
253
well those parts of the signal which are within the range of
the resonant frequency are filtered out.
P254/P253 yields the width of the frequency range at -3dB
weakening, where:
Lower limit frequency = P254 * [Root (1+ 1/(2*P253)^2) -
1/(2*P253) ]
Upper limit frequency = P254 * [Root (1+ 1/(2*P253)^2) +
1/(2*P253) ]
If a quality of 0.0 is input, the pertinent band-stop filter is
switched off, i.e. it lets all frequencies through.
Siemens AG
6SE7087-6QX70 (Edition AL )
SIMOVERT MASTERDRIVES Compendium Motion Control
Data
Read/write
index1: 0
Menus:
Unit: -
- Parameter menu
Indices: 2
+ Control/gating unit
,BDS
+ Speed control
Type: L2 ,K
- Upread/free access
,K
Changeable in:
- Ready to switch on
- Operation enabled
index1: 0,0
Menus:
Min: 0,0
- Parameter menu
Max: 10,0
+ Control/gating unit
Unit: ms
+ Speed control
Indices: 4
- Upread/free access
,FDS
Changeable in:
Type: O2
- Ready to switch on
- Operation enabled
index1: 0,0
Menus:
Min: 0,0
- Parameter menu
Max: 1000,0
- Upread/free access
Unit: ms
Changeable in:
Indices: 4
- Ready to switch on
,FDS
- Operation enabled
Type: O2
Init: 100,0
Menus:
Min: 0,0
- Parameter menu
Max: 150,0
+ Control/gating unit
Unit: %
+ Speed control
Indices: -
- Upread/free access
Type: O2
Changeable in:
- Ready to switch on
Init: 0
Menus:
Unit: -
- Parameter menu
Indices: -
+ Control/gating unit
Type: L2 ,K
+ Speed control
,K
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
index1: 0,0
Menus:
Min: 0,0
- Parameter menu
Max: 3,0
+ Control/gating unit
Unit: -
+ Speed control
Indices: 3
- Upread/free access
Type: O2
Changeable in:
- Ready to switch on
- Operation enabled
42