Parameter
Description
r748
Visualization parameter for displaying the diagnostic
SLB Diagnosis
information for a built-in SIMOLINK board (SLB).
748
Index 1: Number of error-free synchronizing telegrams
Index 2: Number of CRC errors
Index 3: Number of time-out errors
Index 4: Last address actuated
Index 5: Address of the node which transmits the special
telegram, "Time out".
Index 6: Active SYNC interrupt delay 1 = 273 ns
Index 7: Position of the node in the ring
Index 8: Number of nodes in the ring
Index 9: Synchronism deviation (65535 synchronization
not active) should fluctuate between 65515 and 20
Index 10: Corrected pulse period in units of 100 ns (65535
synchronization not active)
Index 11: T0 counter (0 with active synchronization)
Index 12: internal
Index 13: internal
Index 14: Time counter (0 with active synchronization)
Index 15: implemented bus cycle time
Index 16: internal
Index 17: internal
In function diagram 140.7
P749*
Function parameter for entering the node addresses and
SLB Read Addr
channels from which a built-in SIMOLINK board (SLB) is
to read out data. The places before the comma in the
749
input value define the node address and the places after
the comma define the channel.
Example:
2.0 = node address 2, Channel 0
Writing access is set in P740.
r750
Visualization parameter for the data received via
SLB Rcv Data
SIMOLINK.
750
P751*
BICO parameter for selecting the connectors which are to
S.SLBTrnsData
be transmitted by a SIMOLINK board (SLB). In addition to
the connectors themselves, their place in the transmitted
751
telegram is also defined.
Index 1: Channel 1, low-word
Index 2: Channel 1, high-word
Index 3: Channel 2, low-word
Index 4: Channel 2, high-word
...
Index 15: Channel 8, low-word
Index 16: Channel 8, high-word
For double-word connectors, the relevant connector
number must be entered in 2 successive indices because,
otherwise, only the higher-value word is transmitted.
r752
Process data transmitted via SIMOLINK in hexadecimal
SLB TrnsData
display
752
P753*
Input for snychronizing counter. This enables time slots to
S.SyncTimeCount
be synchronized above the bus cycle time.
753
Siemens AG
6SE7087-6QX70 (Edition AL )
SIMOVERT MASTERDRIVES Compendium Motion Control
Data
Read/write
Dec.Plc.: 0
Menus:
Unit: -
- Parameter menu
Indices: 17
+ SIMOLINK
Type: O2
- Upread/free access
index1: 0,0
Menus:
Min: 0,0
- Parameter menu
Max: 200,7
+ SIMOLINK
Unit: -
- Board configuration
Indices: 8
- Upread/free access
Type: O2
Changeable in:
- Board configuration
- Ready to switch on
Dec.Plc.: 0
Menus:
Unit: -
- Parameter menu
Indices: 16
+ SIMOLINK
Type: L2
- Upread/free access
index1: 0
Menus:
Unit: -
- Parameter menu
Indices: 16
+ SIMOLINK
Type: L2 ,K
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
Dec.Plc.: 0
Menus:
Unit: -
- Parameter menu
Indices: 16
+ SIMOLINK
Type: L2
- Upread/free access
Init: 0
Menus:
Unit: -
- Parameter menu
Indices: -
+ SIMOLINK
Type: L2 ,K
- Upread/free access
Changeable in:
- Ready to switch on