Siemens Simovert Masterdrives Compendium page 1322

Motion control
Hide thumbs Also See for Simovert Masterdrives:
Table of Contents

Advertisement

Parameter
Description
n359
Visualization parameter, input of the technology controller. Dec.Plc.: 1
TeCntr Input
2359
U360*
BICO parameter for selecting the binector for setting the I
S.TeCntr I Set
component of the technology controller.
2360
U361*
BICO parameter for selecting the connector for the setting
S.TeCntr ISetV
value of the technology controller's I component.
2361
U362*
BICO parameter for selecting the connector for the droop
S.TeCntr Droop
of the technology controller.
2362
U363*
BICO parameter for selecting the connector for the gain
S.TeCntrGainAd
adaption of the technology controller.
2363
U364
Function parameter for entering the basic gain of the
TeCntr BasicGain
technology controller.
2364
n365
Visualization parameter, effective gain of the technology
TeCntr Eff.Gain
controller.
2365
U366
Function parameter for entering the integral time of the
TeCntr Time
technology controller.
2366
U367
Function parameter for entering the derivative time of the
TeCntrDerivation
technology controller.
2367
U368*
BICO parameter for selecting the connector for the pre-
S.TeCntr PRE
control signal of the technology controller.
2368
Siemens AG
6SE7087-6QX70 (Edition AL )
SIMOVERT MASTERDRIVES Compendium Motion Control
Data
Read/write
Menus:
Unit: %
- Parameter menu
Indices: -
+ Free blocks
Type: I2
- Upread/free access
Init: 556
Menus:
Unit: -
- Parameter menu
Indices: -
+ Free blocks
Type: L2 ,B
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
Init: 0
Menus:
Unit: -
- Parameter menu
Indices: -
+ Free blocks
Type: L2 ,K
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
Init: 0
Menus:
Unit: -
- Parameter menu
Indices: -
+ Free blocks
Type: L2 ,K
- Upread/free access
Changeable in:
- Ready to switch on
Init: 1
Menus:
Unit: -
- Parameter menu
Indices: -
+ Free blocks
Type: L2 ,K
- Upread/free access
Changeable in:
- Ready to switch on
- Operation enabled
index1: 3,00
Menus:
Min: 0,00
- Parameter menu
Max: 125,00
+ Free blocks
Unit: -
- Upread/free access
Indices: 4
Changeable in:
,FDS
- Ready to switch on
Type: O2
- Operation enabled
Dec.Plc.: 2
Menus:
Unit: -
- Parameter menu
Indices: -
+ Free blocks
Type: I2
- Upread/free access
index1: 3,00
Menus:
Min: 0,00
- Parameter menu
Max: 100,00
+ Free blocks
Unit: s
- Upread/free access
Indices: 4
Changeable in:
,FDS
- Ready to switch on
Type: O2
- Operation enabled
index1: 0,00
Menus:
Min: 0,00
- Parameter menu
Max: 60,00
+ Free blocks
Unit: s
- Upread/free access
Indices: 4
Changeable in:
,FDS
- Ready to switch on
Type: O2
- Operation enabled
Init: 0
Menus:
Unit: -
- Parameter menu
Indices: -
+ Free blocks
Type: L2 ,K
- Upread/free access
Changeable in:
- Ready to switch on
162