Parameter
Description
r828
Visualization parameter for displaying the software codes.
SW ID
With the help of these codes, the compatibility of the
individual software versions can be checked.
828
Index 1: Basic board
not Compact PLUS
Index 2: Optional board in slot A
Index 3: Optional board in slot B
Index 4: Optional board in slot C
Index 5: Optional board in slot D
Index 6: Optional board in slot E
Index 7: Optional board in slot F
Index 8: Optional board in slot G
Index 9: Basic board add-on
For boards without software (e.g. SBR, SLB), 0.0 is
always shown in the corresponding index.
Note: If a T300 or T400 technology board is inserted in
slot D, a communication board in slot G will be indicated
in index 7 (slot F) instead of in index 8.
r829
Visualization parameter for displaying the free calculating
CalcTimeHdroom
time. The reserve of the microprocessor system in the
basic unit is shown in relation to its total calculating
829
capacity in index 1. The free calculating time is influenced
by the set pulse frequency (P340) as well as the number
and processing frequency of the activated function blocks.
The failed time slots from T2 to T10 are counted in Index
2 to Index 10.
Index 11 displays the minimum free number of words of
the DSP stack. Caution! A value of 1 means that the
stack has an overflow!
Index 12 to Index 19 display the remaining calculating
time of the 8 DSP residual time slots. The values refer to
an empirical value of an empty residual time slot.
P830*
The faults entered in this parameter are suppressed.
Fault Mask
Setting note:
- Despite suppression, a pulse disable occurs with some
830
faults (UCE, overcurrent, overvoltage, etc.)
r832
Service parameter, only for Siemens service personnel
Phase Flow
"NL value" of the phase currents of the A/D converter. The
832
hexadecimal values range from 8000h (max. shown
negative current) to 7FF0h (max. shown positive current).
Index 1: Phase L1 (U)
Index 2: Phase L3 (W)
r833
Index 1: Inverter temperature
Drive Temp
Index 2: Rectifier temperature (for AC units with rectifer
temperature sensor - depending on design)
833
P834*
Parameter for entering faults where the drive reacts with a
OFF1 on Fault
ramp-function generator ramp-down (OFF1) prior to a fault
trip in the "Operation" status.
834
Only faults which do not necessitate an immediate trip
can be entered here. The following faults are not
permitted:
F006, F008, F010, F011, F015, F017, F023, F025, F026,
F027
Siemens AG
6SE7087-6QX70 (Edition AL )
SIMOVERT MASTERDRIVES Compendium Motion Control
Data
Read/write
Dec.Plc.: 1
Menus:
Unit: -
- Parameter menu
Indices: 9
+ Diagnostics
Type: O2
+ Messages/displays
- Fixed settings
- Quick parameterization
- Board configuration
- Drive setting
- Download
- Upread/free access
- Power section definition
Dec.Plc.: 0
Menus:
Unit: -
- Parameter menu
Indices: 19
+ Diagnostics
Type: O2
+ Messages/displays
- Upread/free access
index1: 0
Menus:
Min: 0
- Parameter menu
Max: 255
- Upread/free access
Unit: -
Changeable in:
Indices: 5
- Ready to switch on
Type: O2
- Operation enabled
Dec.Plc.: 0
Menus:
Unit: -
- Parameter menu
Indices: 2
- Upread/free access
Type: I2
Dec.Plc.: 0
Menus:
Unit: °C
- Parameter menu
Indices: 4
- Upread/free access
Type: I2
index1: 0
Menus:
Min: 0
- Parameter menu
Max: 65535
- Upread/free access
Unit: -
Changeable in:
Indices: 5
- Ready to switch on
Type: O2
- Operation enabled
109