Vibration Suppression Function Operating Procedure - YASKAWA JUSP-MD D01A Series User Manual

For use with large-capacity models, design and maintenance, multi-winding drive unit, rotational motor, analog voltage and pulse train references, servopack, converter, servomotor
Table of Contents

Advertisement

(3) Detection of Vibration Frequencies
Frequency detection may not be possible if there is not enough vibration to affect the position error.
The detection sensitivity can be adjusted by changing the setting for the remained vibration detection width
(Pn560) which is set as a percentage of the positioning completed width (Pn522). Perform the detection of
vibration frequencies again after adjusting the remained vibration detection width (Pn560).
Remained Vibration Detection Width
Pn560
Setting Range
Note: As a guideline, change the setting 10% at a time. The smaller the set value is, the higher the detection sensitivity will
be. If the value is too small, however, the vibration may not be detected accurately.
The vibration frequencies that are automatically detected may vary somewhat with each positioning operation.
Perform positioning several times and make adjustments while checking the effect of vibration suppression.

6.5.2 Vibration Suppression Function Operating Procedure

The following procedure is used for vibration suppression function.
Vibration suppression function is performed from the digital operator (option) or SigmaWin+. This function
cannot be performed from the panel operator.
The operating procedure from the digital operator is described here.
Σ
Refer to the
-V Series User's Manual, Operation of Digital Operator (No.: SIEP S800000 55) for basic key
operations of the digital operator.
Note: If this function is aborted by pressing the MODE/SET Key, the multi-winding drive unit will continue operating
until the servomotor comes to a stop. After the servomotor stops, the set value will return to the previous value.
The operating flow of the vibration suppression function is shown below.
(1) Operating Flow
Execute steps 1 to 3 in the following page.
Execute steps 4 to 8 in the following page.
Setting Unit
1 to 3000
0.1%
Vibration detected?
Yes
Completed
6.5 Vibration Suppression Function (Fn205)
Position
Factory Setting
400
No
Adjust vibration using measuring device.
Classification
When Enabled
Immediately
Setup
6
6-33