3 Wiring and Connection
3.1.4 General Precautions for Wiring
(1) Power Supply Capacities and Power Losses
The following tables show the power supply capacities and power losses of the multi-winding drive unit,
SERVOPACKs, and converters.
The values are for two pairs of a SERVOPACK and converter.
 Multi-Winding Drive Unit
24 VDC
 SERVOPACKs and Converters
Maximum
Main
Applicable
Circuit
Servomotor
Power
Capacity
Supply
[kW]
Three-
phase
75
400 V
This is the value for the JUSP-RA14-E regenerative resistor unit.
(2) How to Select Molded-case Circuit Breaker and Fuse Capacities
The following tables show the current capacities and inrush current of the multi-winding drive unit, SERVO-
PACKs, and converters.
Use these values as a basis for selecting the molded-case circuit breaker and fuse. The values are for two pairs
of a SERVOPACK and converter.
 Multi-winding Drive Unit
24 VDC
 SERVOPACKs and Converters
Maximum
Main
Applicable
Circuit
Servomo-
Power
tor Capac-
Supply
ity
[kW]
Three-
phase
75
400 V
Input voltage of 24 VDC
Note 1. The rated input current of the SERVOPACK is the nominal value at the rated load.
2. To comply with the low voltage directive, connect a fuse to the input side. Select the fuse or molded-case circuit
3-12
Control Power Supply
Combination of
SERVOPACK and
Converter
SERVO-
Converter
PACK
Model:
Model:
SGDV-
SGDV-COA
101J
5EDA
Control Power Supply
Combination of
SERVOPACK and
Converter
SERVOPACK
Converter
Model:
Model: SGDV-
SGDV-
COA
101J
5EDA
Select the appropriate capacity in accordance with the specified derating.
Cutoff characteristics (25°C): 300% five seconds min.
breaker for the input side from among models that are compliant with UL standards.
The table above also provides the nominal values of current capacity and inrush current. Select a fuse and a
molded-case circuit breaker which meet the cutoff characteristics shown below.
• Main circuit, control circuit: No breaking at three-times the current values of the table for 5 s.
• Inrush current: No breaking at the same current values of the table for 20 ms.
Model JUSP-
MDD
Power Supply
Capacity for
Output
Two SERVO-
Current
PACK-
[Arms]
Converter
Sets [kVA]
128
196
Model JUSP-
MDD
Power
Current Capacity
Supply
Capacity for
Two SERVO-
Main
PACK-
Circuit
Converter
[Arms]
Sets [kVA]
128
128
Control Circuit Power Loss [W]
14.4
Main
Regenerative
Circuit
Resistor
Power
Power Loss
Loss
[W]
[W]
*
2480
(1920)
Current Capacity Control Circuit [Arms]
0.6
Inrush Current
Control
Main
Control
Circuit
Circuit
Circuit
[Arms]
[A0-p]
[A0-p]
*
340
8
Control
Total
Circuit
Power
Power
Loss
Loss
[W]
[W]
192
2672
Rated voltage
Circuit
Fuse
Breaker
[V]
[V]
600
480