3 Wiring and Connection

3.9.3 Setting the Dynamic Brake Unit

3.9.3

Setting the Dynamic Brake Unit

Use the parameters shown in the tables here to make the settings for the following: the servomotor stopping
method when the servo is turned OFF, the output signals used to control the dynamic brake contactor, and the
capacity of the dynamic brake resistor in relation to whether or not a dynamic brake has been connected.
The servomotor stopping method when the servo is turned OFF is set with parameter Pn001.0.
Pn001
When using a dynamic brake resistor from a company other than Yaskawa, set Pn00D.1 (second digit) to 0 or
1 in accordance with the following table depending if an NO or NC contact is used.
Pn00D
The dynamic brake resistor capacity is set with Pn601.
Pn601
(1) Using a Yaskawa Dynamic Brake Unit
• Set Pn001 to n.0.
• Not necessary to set Pn00D
• Set Pn601 to 0.
(2) Using a Dynamic Brake Resistors from Another Company
• Set Pn001 to n.0.
• Set Pn00D to either n.0D or n.1 depending on your system.
• Set Pn601 to 20% of the resistor capacity of your dynamic brake.
(3) Not Using a Dynamic Brake
• Set Pn001 to n.2.
• Not necessary to set Pn00D
• Set Pn601 to 0.
3-42
Parameter
n.0
Stops servomotor by applying DB (dynamic brake).
[Factory
setting]
n.1
Stops servomotor by applying DB and then releases DB.
Stops servomotor without applying DB by coasting to a
n.2
stop.
Parameter
n.0
Enables the control of an NO contactor
[Factory
(The dynamic brake is activated when current is sup-
setting]
plied to the contactor coil.)
Enables the control of an NC contactor
n.1
(The dynamic brake is activated when current is not
supplied to the contactor coil.)
Dynamic Brake Resistor Capacity
Setting Range
0 to SERVOPACK capacity
If the setting of Pn601 is not correct, A.730 or A.731 (dynamic brake overloads) will not
be detected correctly and there is a risk of equipment damage or fire. The Pn601 param-
eter is for the multi-winding drive unit. Do not mistakenly change the SERVOPACK
parameter.
Meaning
Meaning
Speed
Unit
Factory setting
10 W
0
When
Classification
Enabled
After restart
Setup
When
Classification
Enabled
After restart
Setup
Position
Torque
Classification
When Enabled
Immediately
Setup