YASKAWA JUSP-MD D01A Series User Manual page 344

For use with large-capacity models, design and maintenance, multi-winding drive unit, rotational motor, analog voltage and pulse train references, servopack, converter, servomotor
Table of Contents

Advertisement

Parameter
Size
No.
2
Input Signal Selection 1
4th 3rd 2nd 1st
digit digit digit digit
n.    
Pn50A
Setting
Name
Range
0000 to FFF1
Input Signal Allocation Mode
0
Uses the sequence input signal terminals with the factory-set allocations.
1
Changes the sequence input signal allocation for each signal.
Servo ON (/S-ON) Signal Mapping
Signal Polarity: Normal; Servomotor power ON when ON (closed)
Signal Polarity: Reverse; Servomotor power OFF when OFF (open)
0
Active when CN1-40 input signal is ON (closed).
1
Active when CN1-41 input signal is ON (closed).
2
Active when CN1-42 input signal is ON (closed).
3
Active when CN1-43 input signal is ON (closed).
4
Active when CN1-44 input signal is ON (closed).
5
Active when CN1-45 input signal is ON (closed).
6
Active when CN1-46 input signal is ON (closed).
7
Always active (fixed).
8
Not active (fixed).
9
Active when CN1-40 input signal is OFF (open).
A
Active when CN1-41 input signal is OFF (open).
B
Active when CN1-42 input signal is OFF (open).
C
Active when CN1-43 input signal is OFF (open).
D
Active when CN1-44 input signal is OFF (open).
E
Active when CN1-45 input signal is OFF (open).
F
Active when CN1-46 input signal is OFF (open).
/P-CON Signal Mapping (P control when ON (closed))
0 to F
Same as Servo ON Signal (/S-ON) Mapping.
P-OT Signal Mapping (Forward run prohibited when OFF (open))
0
Forward run allowed when CN1-40 input signal is ON (closed).
1
Forward run allowed when CN1-41 input signal is ON (closed).
2
Forward run allowed when CN1-42 input signal is ON (closed).
3
Forward run allowed when CN1-43 input signal is ON (closed).
4
Forward run allowed when CN1-44 input signal is ON (closed).
5
Forward run allowed when CN1-45 input signal is ON (closed).
6
Forward run allowed when CN1-46 input signal is ON (closed).
7
Forward run prohibited.
8
Forward run allowed.
9
Forward run allowed when CN1-40 input signal is OFF (open).
A
Forward run allowed when CN1-41 input signal is OFF (open).
B
Forward run allowed when CN1-42 input signal is OFF (open).
C
Forward run allowed when CN1-43 input signal is OFF (open).
D
Forward run allowed when CN1-44 input signal is OFF (open).
E
Forward run allowed when CN1-45 input signal is OFF (open).
F
Forward run allowed when CN1-46 input signal is OFF (open).
Factory
Units
When Enabled
Setting
2100
After restart
10.2 List of Parameters
(cont'd)
Classifi-
Reference
cation
Section
Setup
Reference
Section
3.4.1
Reference
Section
5.2.1
Reference
Section
6.7.4
Reference
Section
5.2.3
10
10-25

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sigma-v seriesSgdv-j seriesSgmvvSgdv-coa

Table of Contents