Preparations; Applicable Tools; Operating Procedure - YASKAWA SERVOPACK Sigma 7S Series Supplementary Manual

Ac servo drive
Table of Contents

Advertisement

2.1.2

Preparations

Check the following settings before you execute anti-resonance control adjustment.
• The tuning-less function must be disabled (Pn170 = n.0).
• The test without a motor function must be disabled (Pn00C = n.0).
• The control method must not be set to torque control.
• The parameters must not be write prohibited.
2.1.3

Applicable Tools

The following table lists the tools that you can use to perform anti-resonance control adjust-
ment and the applicable tool functions.
Tool
Panel Operator
Digital Operator
SigmaWin+
2.1.4

Operating Procedure

To execute anti-resonance control adjustment, an operation reference is input, and the adjust-
ment is executed while vibration is occurring.
The following methods can be used to execute anti-resonance control adjustment.
• To automatically detect the vibration frequency
• To manually set the vibration frequency
Use the following procedure.
 Before you execute anti-resonance control adjustment, check the information provided in
the SigmaWin+ operating manual.
Observe the following precautions.
• Make sure that you can perform an emergency stop at any time.
Parameters will be set automatically when anti-resonance control adjustment is executed. This
may greatly affect the response before and after execution. Make sure that you can perform an
emergency stop (to turn OFF the power supply) at any time.
• Set the moment of inertia correctly before you execute anti-resonance control adjustment.
If the setting greatly differs from the actual moment of inertia, effective vibration reduction may
not be possible.
• If you have already performed anti-resonance control adjustment and then you change the fre-
quency, the current anti-resonance control effect may be lost. Caution is particularly required
when automatically detecting the vibration frequency.
• If effective vibration reduction is not achieved even after you execute anti-resonance control
adjustment, cancel the function and lower the control gain by using a different method, such as
custom tuning.
• Perform custom tuning separately if required to increase the response after performing anti-reso-
nance control adjustment.
If the servo gain is increased, e.g., when custom tuning is performed, vibration may occur again.
If that occurs, perform anti-resonance control adjustment again to fine-tune the parameters.
1.
Perform steps 1 to 7 of the procedure for custom tuning.
For details, refer to the manual for your SERVOPACK.
Function
You cannot execute anti-resonance control adjustment from the Panel Operator.
Fn204
Tuning - Tuning
CAUTION
2.1 Anti-Resonance Control Adjustment

2.1.2 Preparations

Operating Procedure Reference
Σ-7-Series Digital Operator Operating Man-
ual (Manual No.: SIEP S800001 33)
2.1.4 Operating Procedure on page 2-3
2
2-3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Servopack sigma 7w series

Table of Contents