Application example, "Read and write to parameters"
Further information is provided on the Internet:
7.6

Drive control via Ethernet/IP

7.6.1

Configuring communication via Ethernet/IP

Overview
Ethernet/IP is real-time Ethernet, and is mainly used in automation technology.
Function description
To configure the converter's communication via Ethernet/IP, you must set the following
parameters:
Procedure
1. p2030 = 10
2. The following parameters must match your Ethernet configuration:
– p8921 = IP address
– p8922 = default gateway
– p8923 = subnet mask
– p8920 = station name
3. p8925 = 2
4. Select the Ethernet/IP profile:
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA
Overview of the manuals (Page 588)
Application examples (https://support.industry.siemens.com/cs/ww/en/view/29157692)
SINAMICS profile
p8980 = 0
Use p0922 to select the appro‐
priate telegram.
Telegrams (Page 143)
ODVA AC/DC drive profile
p8980 = 1
p0922 = 1: The converter communicates via telegram 1. Other
telegrams are not possible. If necessary, however, you can extend
the telegram 1.
Expanding or freely interconnecting telegrams (Page 154)
If necessary, set the following parameters:
p8981
p8982
p8983
Advanced commissioning
7.6 Drive control via Ethernet/IP
157