Important circuit information

Warning
!
Terminal 63 (pulse enable) and/or terminal 48 (start terminal, contactor control)
must be de–energized before the system is powered–up or down using the
main switch or a line contactor!
Warning
!
If the NE is connected up using a 6–conductor connection (the supply connec-
tion for the electronics power supply is separate from that of the power connec-
tion), then the jumper, included as standard, in connector X181 must be remo-
ved.
The coil circuit to reliably de–energize the line contactor when an error condition
occurs, can be isolated via terminals NS1, NS2.
The terminals must always be jumpered in operation! The DC link will not
be pre–charged if the connection is missing when the unit is powered–up.
The NS1, NS2 connection may only be switched when terminal 48 is ope-
ned (or simultaneously with terminal 48).
Warning
!
If the power supply is supplied through P500, M500 at connector X181, a
6–conductor connection (electronic power supply connection before the HF
commutating reactor) is not permissible.
Connection
Possibility to connect–up the
electronics power supply
Siemens AG 1998 All Rights reserved
SIMODRIVE 611 (PJ)
Electrical isolation of the line supply from the power circuit of the drive group
via terminals NS1, NS2.
Electronics power supply
connection X181
2U1––2W1
2U1––2W1
6SN1197–0AA00 02.98 Edition
Component
1U1––1W1
Not permissible
Supply L1 to L3
1U2––1W2
Connect–up
NE module
Comments