Motor data identification
After entering the motor data, the wizard requests that the motor data identification is activated. This is
recommended for a verification and optimization of the data that you have entered. The motor data
identification initiates a "measurement" of the connected motor. In the process, the data previously cal-
culated in the converter are compared to the actual motor data and adapted to one another.
Activating motor data identification (P1900)
• Press OK to confirm MOT ID
• Change the displayed value to 1 by pressing UP
Motor data identification only starts after the basic commissioning sequence has been completed
and the motor is switched on the first time!
The motor data identification can take several minutes. Do not interrupt the process.
Specifying application parameters using MacroParameter
In the next step, pre-defined settings for the converter interfaces can be activated. This is stored in
parameter number 15 and indicated by MAc PAr for macro parameterization. For example, the converter
offers different pre-defined macros for setting the command and setpoint sources (see Page 20/21).
Activating pre-defined settings (P15) e.g. for command and setpoint source
• Press OK to activate macro parameterization MAc PAr
• Macro 12 (Std ASP) is displayed, it determines DI 0 for the command source and the
analogue input 0 for the setpoint source
• Leave the value and confirm by pressing OK
OK
The converter can now be switched on using digital input DI 0.
AI0 (0-10V) is selected as the setpoint source.
OK
OK