Motor Connection Data; Motor Cable Length; Operational Functionality And Motor Cable Length - ABB ACS180-04S-03A7-1 Hardware Manual

Table of Contents

Advertisement

130 Technical data
Rated conditional
short-circuit current
I cc (IEC 61800-5-1)
Short-circuit current
protection
(UL 61800-5-1, CSA
C22.2 No. 274-13)
Mains choke
Frequency (f1)
Imbalance
Fundamental power
factor (cos phi)

Motor connection data

Motor type
Voltage (U2)
Short-circuit protec-
tion (IEC 61800-5-1,
UL 61800-5-1)
Frequency (f2)
Frequency resolution
Current
Switching frequency

Motor cable length

Operational functionality and motor cable length

The drive is designed to operate with optimum performance with the following
maximum motor cable lengths. The motor cable lengths may be extended with
output chokes as shown in the table.
65 kA when protected by fuses given in the fuse tables.
US and Canada: The drive is suitable for use on a circuit capable of
delivering not more than 100 kA symmetrical amperes (rms) at 480
V maximum when protected by fuses given in the fuse table. The
drive is also suitable for use on a circuit capable of delivering not
more than 65 kA symmetrical amperes (rms) at 480V maximum when
protected by the specific manual self-protected Type E combination
motor controllers given in the manual self-protected combination
motor controller table, provided the drive is mounted within an en-
closure of adequate minimum volume, and the assembly complies
with all applicable footnotes of the table.
Use a mains choke if the network's line impedance is low (less than
0.3% total system impedance of all the ACS180 drives in the install-
ation), or has voltage imbalance, or harmonic distortion that make
the input current bigger than the nominal input current ratings. You
can use one choke for several drives as long as the choke current
rating is not exceeded.
47 to 63 Hz, maximum rate of change 17%/s
Max. ±3% of nominal phase to phase input voltage
0.98 (at nominal load)
Asynchronous induction motor or permanent magnet synchronous
motor
0 to U 1 , 3-phase symmetrical, U max at the field weakening point
The motor output is short-circuit proof by IEC 61800-5-1 and UL
61800-5-1.
0...599 Hz
0.01 Hz
See the rating information.
4, 8, or 12 kHz