4.5 Quality Management
Under the System tab, you can set Notifications for Minor and Major Alarms/Clearances. The
temperature readouts used for the Alarms are generated by the CPU temperature sensor .
Also, you can set the temperature
threshold value
for Minor/Major alarms, and define a
retry
value
by determining how many readings (1/min.) the temperature must exceed the threshold
value before an alarm/clearance is triggered.
The default temperature threshold value for both Minor, and Major Alarms is 100°C. With sim
ultaneous alarm triggerings, the Major Alarm will override the Minor Alarm, i.e. you will be
notified only about the Major Alarm. If you want to be notified early about a rise in tem
perature, a recommended setting for the Minor Alarm temperature would be 90°C. Please note
that it is not advisable to set the Major Alarm temperature to a value higher than 100°C.
CHAPTER
•
4
SecureSync User Reference Guide Rev. 23
286