Mx2010 Dc Power Distribution (240 V China) Description - Juniper MX2010 Hardware Manual

Universal routing platform
Hide thumbs Also See for MX2010:
Table of Contents

Advertisement

RELATED DOCUMENTATION
MX2010 DC Power Distribution Module (-48 V) Description | 111
MX2010 DC Power Supply Module (-48 V) Description | 116
Connecting Power to a DC-Powered MX2010 Router with Power Distribution Modules (-48 V) | 304
Installing MX2010 DC Power Supply Modules
Replacing an MX2010 DC Power Distribution Module Cable | 496
Connecting an MX2010 DC Power Distribution Module Cable | 498
DC Power Cable Specifications for the MX2010 Router | 209

MX2010 DC Power Distribution (240 V China) Description

Most sites distribute DC power through a main conduit that leads to frame-mounting DC power distribution
panels, one of which might be located at a location near the rack that houses the router. The 240 V China
PDM cable connects the PDM to the power distribution panel and safety ground connection.
The PSMs can be connected to two separate feeds from different sources that are used for feed redundancy.
There are two PDMs located in slots PDM0/Input0 and PDM1/Input1 that are capable of carrying nine
feeds each. Each feed is connected from one source to one PDM and feeds from the other source to the
second PDM of the DC power system. This configuration balances power draw for the system by using
the commonly deployed A/B feed redundancy.
Each system provides N+1 PSM redundancy along with N+N feed redundancy. If both DC feeds are
available, operating power draws from the feed with higher voltage. ). Each set of power cables powers a
single DC PSM and is capable of delivering 2500 W of power. If feeds that connect to one PDM fail in a
redundant configuration, the other feed starts to provide full power.
Figure 74 on page 200
shows a typical DC source cabling arrangement.
199