MX2010 Router Environmental Specifications
Table 43 on page 141
specifies the environmental specifications required for normal router operation. In
addition, the site should be as dust-free as possible.
Table 43: Router Environmental Specifications
Description
Relative humidity
Temperature
Seismic
Maximum thermal output
NOTE:
Install the router only in restricted areas, such as dedicated equipment rooms and
equipment closets, in accordance with Articles 110-16, 110-17, and 110-18 of the National
Electrical Code, ANSI/NFPA 70.
RELATED DOCUMENTATION
Value
Normal operation ensured in relative humidity range of 5%
through 90%, noncondensing
Normal operation ensured in temperature range of 32°F (0°C)
through 104°F (40°C)
Nonoperating storage temperature in shipping container:
–40°F (–40°C) through 158°F (70°C)
Designed to meet Telcordia Technologies Zone 4 earthquake
requirements
AC input power: 129,280 BTU/hour
DC input power: 129,280 BTU/hour