For more information about AC PDM input power mapping, see
Distribution Modules to AC Power Supply Modules on MX2000 Routers" on page
CAUTION:
(4.5 m) in length, to comply with National Electrical Code (NEC) Sections 400-8 (NFPA
75, 5-2.2) and 210-52, and Canadian Electrical Code (CEC) Section 4-010(3). The cords
supplied with the router are in compliance.
CAUTION:
location. It has a separate protective earthing terminal (sized for UNC 1/4-20 ground
lugs) provided on the chassis in addition to the grounding pin on the power cord. This
separate protective earthing terminal must be permanently connected to earth.
CAUTION:
drape where people could trip on them.
NOTE:
Three-phase power cords provided with the router are approximately 14.75 ft (4.5 m)
in length. Single–phase power cords provided with the router are approximately 8.2 ft (2.5 m)
in length.
Table 54 on page 171
and
region supported.
Figure 64 on page 172
Delta and Wye AC power cords.
Table 54: Three-Phase Delta and Wye AC Power Cord Specifications
Region
North America
Europe
In North America, AC power cords must not exceed approximately 14.75 ft
The router is pluggable type A equipment installed in a restricted-access
Power cords and cables must not block access to device components or
Table 55 on page 172
provide specifications for the AC power cords for each
and
Figure 65 on page 172
Model Number
CBL-MX2000-3PH-DELTA
CBL-MX2000-3PH-WYE
"Mapping Input Power from AC Power
185.
illustrate the plug on the three-phase
171