Dc Power Supply Description; Mx5, Mx10, Mx40, And Mx80 Power Supply Led; Figure 17: Ac Power Supply; Figure 18: Dc Power Supply - Juniper MX5 Hardware Manual

Universal routing platform
Hide thumbs Also See for MX5:
Table of Contents

Advertisement

MX5, MX10, MX40, and MX80 Universal Routing Platforms Hardware Guide

MX5, MX10, MX40, and MX80 Power Supply LED

34

Figure 17: AC Power Supply

Ejector lever
Handle
AC power
inlet
WARNING:
The router is pluggable type A equipment installed in a
restricted-access location. It has a separate protective earthing terminal
(sized for SAE 10-32 ground screws) provided on the chassis in addition to
the grounding pin of the power supply cord. This separate protective earthing
terminal must be permanently connected to earth.

DC Power Supply Description

Each DC power supply has a handle, an ejection lever, a power switch, a status LED, and
a terminal block that provides a single DC input (–48 VDC and return) that requires a
dedicated customer site circuit breaker. We recommend that you use a dedicated
customer site circuit breaker rated for 13 A (–48 VDC) minimum, or as required by local
code.
Figure 18 on page 34

Figure 18: DC Power Supply

Ejector lever
Handle
DC
terminal
block
Each power supply has a bi-color status LED located above the power switch on the
power supply.
Status LED
Power
switch
shows the power supply.
Status LED
Power
switch
Copyright © 2019, Juniper Networks, Inc.